The flush-mounted NSA7000 series network sensor with LCD is an electronic zone sensor designed to function directly with Johnson Controls® BACnet® MS/ TP digital controllers in heating, ventilating and air conditioning (HVAC) systems. Models in this series monitor the temperature set point, zone temperature and humidity, and transmit this data to a field controller on the sensor actuator (SA) bus.NSA-FHR71X3-0 can toggle between temperature and RH on the display, and has the capability to set the desired default display to either temperature or RH. A fan mode push button is included in NSA-FTD70X3-0 to set the desired fan speed (OFF-LOW-MED-HIGH-AUTO). Model Number :
NSA-FHN7001-0, NSA-FTD7003-0, NSA-FTB7003-0, NSA-FHR7103-0, NSA-FHN7011-0, NSA-FTD7013-0, NSA-FTB7013-0, NSA-FHR7113-0, NSA-FHN7021-0, NSA-FTD7023-0
The Variable Air Volume (VAV) Controller is an electronic device for digital control of single duct, dual duct, fan powered, and supply/exhaust VAV box configurations. Along with the capability of standalone control of the VAV box, the controller can also integrate the control of the room or zone baseboard heat and lighting logic. You may use the VAV as a standalone controller, or connected to the Metasys Network through a Network Control Module (NCM) or Companion Model Number :
AS-VAV110-1, AS-VAV140-1, AS-VAV111-1, AS-VAV141-1
FX-PCVs are programmable, digital controllers tailored for VAV box control applications that communicate via the BACnet® Master-Slave/Token-Passing (MS/TP) protocol. The FX-PCV controllers feature an integral digital pressure sensor, an integral damper actuator,
and a 32-bit microprocessor.
The FX-PCV1615 and FX-PCV1617 models are designed for cooling only VAV box control applications, while the FX-PCV1630 and FX-PCV1632 models are better suited for cooling with reheat VAV and fan control applications. The FX-PCV1617 and FX-PCV1632 models
are only available in Asian markets. Model Number :
FX-PCV1615-0, FX-PCV1630-0, FX-PCV1617-01, FX-PCV1617-01
The CV series controllers are designed for variable air volume (VAV) box applications.
CV series controllers feature 14 preloaded standard applications to allow this controller to operate standard VAV box equipment with a proven energy- efficient sequence of operation, without the need for programming. For information on configuring a CV series controller to use a preloaded application.
CV series controllers feature an integral damper actuator, a digital Differential Pressure Transmitter (DPT) sensor, and a 32-bit microprocessor. The CVM03050-0P and CVE03050-0P models feature an integral potentiometer to sense actual VAV box damper position Model Number :
F4-CVM03050-0, F4-CVM03050-0P, F4-CVE03050-0P
The VMA1615, VMA1630, VMA1832, and VMA1930 (32-bit) controllers feature an integral digital differential pressure transducer (DPT), an integral damper actuator, and a 32-bit microprocessor. The controllers' small package size facilitates quick field installation and efficient use of space, while not compromising high-tech control performance. These controllers easily adapt NS Series Network Sensors for zone and discharge air temperature sensing.
The VMA1930 programmable controller uses BACnet/IP networking for higher speed communication with the Controller Configuration Tool (CCT) and improved bandwidth. This gives you more flexibility in choosing controllers for your site's specific needs
VAV 1717 / 1732 / 1507 CONTROLLER SERIES – JOHNSON CONTROLS
The VAV1717 and VAV1732 controllers are designed for Variable Air Volume (VAV) applications. These controllers operate on an RS-485 BACnet® MS/TP bus as BACnet Application Specific Controllers (B-ASCs).
These controllers feature 10 preloaded standard applications that operate standard VAV box equipment with a proven energy-efficient sequence of operation, without the need for programming. However, the controllers are also fully programmable using the Controller Configuration Tool (CCT), which provides the flexibility to create custom control sequences.
These controllers feature a combination of an integral digital differential pressure transducer (DPT), a damper actuator, and a 32-bit microprocessor. The small package size of the controllers facilitates quick field installation and efficient use of space without compromising hightech control performance..
The Metasys® Variable Air Volume Single Duct terminal Unit system is designed to accept direct digital controls (DDC) for pressure independent operation. Also are a single source quality VAV Box solution and a complete set of associated controls into one cost effective package. The package is available in Basic VAV or Reheat VAV systems and with options for the temperature sensor..
Johnson Controls VAV box which is design and build in accordance with ARI standard 880-89 and ANSI/ASHRAE 130-1996 for the laboratory test.
In order to provides complete solution to our valuable customer. Johnson Controls offer wide range of installation accessories product, e.g. Attenuator, Multi-Outlet Attenuator, Round Discharge Collar, Hot Water Heating Coil and Electrical Heater
Model TSS/TSL terminals provide variable air volume (VAV) control beyond the typical single duct box. They are specifically designed for precise air delivery throughout the entire operating
range, regardless of the installed inlet conditions. They also offer improved space comfort and flexibility for a wide variety of HVAC applications.TSS/TSL terminals take advantage of typical benefits provided by single duct units, while performing at extremely low sound levels. This is critical in today’s buildings, where occupants are placing more emphasis on indoor acoustics.
The TSS/TSL terminal provides the ultimate in airflow control with the patented FlowStar TM
airflow sensor. No other sensor in the industry can match the FlowStar’s ability to quietly and precisely measure airflow. Accurate airflow measurement is the basis for airflow control.
FCU / AHU VAN CÂN BẰNG VPS SERIES – JOHNSON CONTROLS
VPS Static Balancing Valve, DN15 to DN300
Y-pattern valves having characterized throttling disk tend towards equal percentage performance, fitted with Integral square edged entrance orifice plate and insertion test points. Double regulating feature allows valve to be set with an Allen key. Operation of the valve is by means of the Microset hand wheel. All valves operate from close to fully open with complete turns of the handwheel. The digit in the outer window indicates tenths of a turn
DN65 to DN150 valves operate from close to fully open with 8 complete turns of the handwheel, 12 turns for DN200 to DN250 and 18 turns for DN300 . The digit in the outer tenths of a turn. Model Number :
VPS015-C, VPS020-C, VPS025-C, VPS032-C, VPS040-C, VPS050-C, VPS065-C, VPS080-C, VPS100-C, VPS125-C, VPS150-C, VPS200-C, VPS250-C, VPS300-C
FCU VAN CÂN BẰNG, ĐIỀU KHIỂN VPF SERIES – JOHNSON CONTROLS
VPF series Motorized dynamic balancing valve for FCU DN15 TO DN25
Motorized dynamic balancing valves are used in FCU system or as zone valve control. VA-7078-23 actuator is used with VPF series balancing valve for On/Off control of the fan coil unit and the flow range is 0.43 - 1.76m3/h
Rated Pressure 25bar, Close-off Pressure 250kPa, 230 VAC ±10%(50/60 Hz) Model Number :
VPF015L02-C, VPF020L02-C, VPF020L04-C, VPF020H06-C, VPF020H08-C, VPF025L04-C, VPF025H06-C, VPF025H10-C
FCU / AHU VAN CÂN BẰNG VPD SERIES – JOHNSON CONTROLS
VPD Constant Flow Rate Dynamic Balancing Valve DN15 TO DN40
The VPD dynamic balancing valves are designed as a constant flow valve which provides easy and reliable balancing of the system, regardless of any fluctuations in the differential pressure of the system. Common applications for dynamic balancing valve includes terminal unit or branch balancing, air handling unit flow control in common HVAC system, multiple chillers or pump balancing system in high-rise buildings
Model Number :
VPD015L01-C, VPD020L04-C, VPD025L03-C, VPD032L10-C, VPD040L14-C
FCU/ AHU VAN ĐIỀU KHIỂN, CÂN BẰNG VPA SERIES – JOHNSON CONTROLS
Pressure Independent Balancing and Control Valve - VPA series Dynamic Balancing Valve
and VAP Actuator DN25...150, PN16.
Pressure Independent Balancing and Control Valve includes two functional control elements: Dynamic Balancing Valve and Motorized
The built-in balancing tube has more compact structure and can avoid damages during shipping and installation compared to the external Model Number :
VPA025-C, VPA032-C, VPA040-C, VPA050B-C, VPA050-C, VPA065-C, VPA080-C, VPA100-C, VPA125-C, VPA150-C, VAP500-24-C, VAP1000-24-C, VAP3000-24-C
VAN ĐIỀU KHIỂN, ĐO ĐẾM NĂNG LƯỢNG VP3000 SERIES – JOHNSON CONTROLS
VP3000 Series Electronic Pressure-Independent PICVs
Use VP3000 Series pressure-independent control valves (PICVs) in HVAC systems with variable flow rates. They are designed for air conditioning ceiling units, air handling units, two-pipe and four-pipe fan coil units, heat exchangers, and other similar applications
Integrated flow measurement, Optional integrated ΔT measurement, MP Multi Protocol: Modbus RTU and BACnet MS/TP, Wireless commissioning through Bluetooth®. Model Number :
VP3C2P20B, VP3N6xxxB , VP3MB2DxxxC , VP3UB2FxxxC
VAN BƯỚM ĐIỀU KHIỂN CHO HỆ CHILLER VF6000 SERIES – JOHNSON CONTROLS
The VF6000 Series Butterfly Valve and VA300/VA200 Actuator shut off or regulate the flow of hot or chilled water in a HVAC system.
This series covers models from DN50 to DN1000 with either on/off or modulating output via various actuators Model Number :
VF6461xx-C , VF6431xx-C, VA9320 , VA9335, VA301xxx-C, VA302xxx-C, VA303xxx-C , VA304xxx-C, VA305xxx-C , VA306xxx-C, VA307xxx-C, VA308xxx-C, VA309xxx-C, VA310xxx-C, VA311xxx-C, VA312xxx-C
VAN BƯỚM ĐIỀU KHIỂN CHO HỆ CHILLER VF3000 SERIES – JOHNSON CONTROLS
VF3000 series Butterfly Valves and VA5000 series Electric Actuators
DN50...1000, PN16.
The VF3000 series butterfly valves are used for shutting off or regulating the flow of hot or chilled water in a HVAC system. Mounted with VA5000 series actuators, the valves operate with a wide range of applications, including two-position and Model Number :
VA5003xxx-C, VA5005xxx-C, VA5008xxx-C, VA5020xxx-C , VA5040xxx-C , VA5060xxx-C , VA5080xxx-C , VA5100xxx-C , VA5170xxx-C, VA5230xxx-C, VA5350xxx-C, VA5500xxx-C, VA5800xxx-C
VAN BƯỚM CHO HỆ CHILLER VF3000 SERIES –JOHNSON CONTROLS
DN50...1000, PN16.
The VF3000 series manual butterfly valves are designed to manually shut off or modulate the flow of hot or chilled water in HVAC system.Medium Hot / chilled water, glycol solution (<50% concentration) in HVAC system Medium temperature -10℃~120℃ Valve Body Ductile iron (GGG40) Stem Stainless steel Valve disc Ductile iron (GGG40) with Nylon 11 coating or Stainless steel (SS304) Model Number :
VF3461xx-MC , VF3431xx-MC